Making lithium-ion
battery systems safer.

2021_Pyrophobic_LithiumPrevent

Product Description

LithiumPrevent is a passive fire containment solution that makes lithium-ion battery systems safer by preventing thermal runaway propagation. Including LithiumPrevent in the design of an OEM’s battery system is proven to achieve the industry’s toughest fire safety test standards. The base material is a proprietary intumescing polymer that can be extruded or injection molded to meet application requirements.

LithiumPrevent provides fire safety solutions for problems associated with lithium-ion batteries:

• Contains thermal runaway at the cell or module level
• Provides thermal separation between cells or modules
• Controls explosive events
• Prevents cascading fire propagation
• Prevents transfer of internal heat to outside combustibles

Lithium Prevent Features

• A durable polymer composite material
• Can be injection molded or overmolded to almost any shape or size
• Extrudable into sheets for various applications
• Several commercially available formulations
• Electrically non-conductive

• Separation between cells or modules segregates runaway events
• Designed to manage an explosive event by venting both ejecta and gases
• Several commercially available formulations
• Excellent processability

Properties

State

Solid

Colour

White

Specific Gravity

1.54g/ml

Melting Point

129 ° C

Start Expansion  Temperature

200 ° C

Specific Gravity

2-3

original volume

Flammability Control and Toxicity Outgassing

Outgassing in a Vacuum Environment

0.03% Volatile Condensible Material

NASA STD 6016, SP-R-0022A
(ASTM E 595)

Flammability Characteristics

None to Small

NASA STD 6001

Upward Flame Propogation

Results were less than  reporting limit

NASA STD 6001

Performance Data

ASTM Test Standard

LP200

ASTM D2240  –  Shore Hardness

D67

ASTM D792  –  Density Method A

1.54 gm/cm3

ASTM D638  – Tensile Strength

13.9 MPa

ASTM D746 – Brittleness Temp by Impact

>-5° C

ASTM D257 – Volume Resistivity

Avg 8.59E+13  Ohms /cm

ASTM D635 –Horizontal Burning

HB – 0

UL94 – Vertical Burning

V – 0

ASTM E2585 – Thermal Diffusivity

0.142 mm2/s  0.259 W/(m.k)

ASTM D3755 – Dielectric Strength

Breakdown Volt. >10 kV  Dielectric Str >2.65 kV/mm

Start Expansion – Pyrophobic Internal

200°C

Volumetric Expansion – Pyrophobic Internal

2 – 3 X